Home » Dent Instruments ELITEpro SP Recording Power Meter
Dent Instruments ELITEpro SP Recording Power Meter
- Single and Three Phase up to 600V and 6000A
- Measure V, A, W, kWh, VA, VAr and PF
- Min, max, average and alarms
- 8MB Memory
- ELOG software for easy analysis and report creation





The Next Generation Energy Logger from Dent Instruments
The Dent Instruments ELITEpro SP is a complete solution for pinpointing electric usage and quantifying energy usage. It is capable of measuring, storing, and analyzing electrical consumption data which is derived from the voltage and current inputs. The ELITEpro SP uses direct connections to each phase of the voltage and various interchangeable CT options such as split-core current transformers or fl exible RoCoils™ (for large loads or large cables and bussbars) to monitor current on each phase.These meters can capture kWh/kW energy and demand data as well as virtually all relevant energy parameters for diagnostics and monitoring on three-phase or single-phase circuit installations. Electrical load diagnostic parameters such as power factor (both Apparent and Displacement) are captured in addition to energy and demand values.
The ELITEpro SP flexibility, size, and ease-of-use make them ideal tools for gathering detailed consumption information in commercial, industrial, government and retail environments.
Anatomy of ELITEpro SP

Line Powered with Reduced Impact on the Environment
The ELITEpro SP is powered directly from the phases of the service being measured. It incorporates a broadband power supply which operates on virtually any 60-600V service. You will not have to worry about constantly changing or recharging batteries, nor finding an external power source at the job site. And you will avoid the negative environmental impact of disposing of batteries containing rare earth materials that are difficult to recycle or reclaim.Memory for Extended Recording
Measurements are stored in on-board memory at recording intervals selected by the user, which can be as short as one second or as long as once every 24 hours.The ELITEpro SP has 8MB of internal non-volatile memory, which allows for long-term logging sessions. For example, with a WYE setup and recording all available system measurements ON with 2 minute integration interval, the ELITEpro SP can log for for over 80 days!Fast Sampling Rate Captures Power Quality Data
Regardless of the user-selectable recording interval, the ELITEpro SP has a waveform sampling frequency of 12 kHz. This is the number of data points the logger samples on each AC waveform (200 points per cycle at 60 Hz; 240 points per cycle at 50 Hz). The channel sampling rate is 8 Hz or every 125 mSec. This fast sampling rate allows for real-time display of voltage and current waveforms and harmonics.Exclusive CT Phase Error Correction
All CTs exhibit both a ratio error and phase shift error. The CT phase error results from the phase relationship of the input versus output signal difference. This inherent phase angle error affects power readings if left uncorrected. When using CTs with a known phase angle error, the ELITEpro SP can correct for this error—making your calculations more accurate, particularly on loads with low power factor.Wide Selection of CTs
The ELITEpro SP uses various interchangeable CT options such as split-core, clamp-on, or fl exible RoCoil™ current transformers. With the ELITEpro SP comes embedded Rogowski coil CT amplifi er/integrator circuitry—no need to provide external power to the CTs. All DENT CTs are internally shunted for intrinsically safe operation on energized conductors. Special high-accuracy CTs are available for existing CT secondary monitoring. The ELITEpro SP can monitor up to four single-phase loads, two three-phase (3-wire) Delta loads or one three-phase (4-wire) WYE load.Scroll down to view optional accessories you can get with your ELITEpro SP.
The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
- Works on single or 3-phase loads on 0-600V (AC or DC) voltage services. Measures up to four channels of current from 0-6,000 amps (AC current only).
- Line-powered – no need for batteries or external power source.
- User-selectable recording intervals as short as every 1 second.
- 8MB non-volatile memory standard for up to months of recording time.
- Better than 1% accuracy (<0.2% typical).
- Fast USB connection.
- Simple yet powerful Windows-based ELOG™ software package for setup, data retrieval, and analysis. Easy data exporting to almost any analysis program such as Excel® and Access®.
- Easy setup and installs in minutes. Patented PhaseChek LED indicators ensure correct CT orientation at installation.Rugged and compact—easily fi ts inside breaker panels and switch gear.
| Technical | |
| Service Type | Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
| Voltage Channels | 3 Channels, CAT III, 0-600 VAC or 850 VDC (line-to-line) |
| Current Channels | 4 Channels, .67 VAC max, 333 mV full scale CTs |
| Maximum Current Input | 200% of current transducer rating |
| Measurement Type | True RMS using high-speed digital signal processing (DSP) |
| Live Frequency | 50/60/400 Hz |
| Waveform Sampling | 12 kHz |
| Channel Sampling Rate | .125 |
| Measurements | Volts, Amps, Amp-Hrs (Ah), kW, kWh, kVARh, kVA, kVAh, Displacement Power Factor (dPF). All parameters for each phase and for system total. |
| Accuracy | Better than 1% (<0.2% typical) for V, A, kW, kVAR, kVA, PF |
| Resolution | 0.01 Amp, 0.1 Volt, 1 Watt, 1 VAR, 1 VA, 0.01 PF |
| LED Indicators | Bi-colors (red and green): 1 LED to indicate communication, 4 LEDs for correct phasing (PhaseChek™: green when voltage and current on the same phase; red when incorrectly wired.) 2 LED Output indicators. |
| Pulse Output | Open collector with 10K ohm pull up to 5V, 75 mA max current |
| Power | |
| Line Power | From L1 Phase to L2 Phase. 60-600VAC CAT III 50/60 Hz, 70 mA max. Non-user replaceable .5 Amp internal fuse protection |
| Power In | 6-10 VDC, 500 mA |
| Power Out | 6 VDC, 200 mA max |
| Communications | |
| USB Direct Connection | 1.8 M (6 FT) A-TO-B USB Cable (included) |
| Mechanical | |
| Operating Temperature | -7 to + 60 °C (20 to 140 °F) |
| Operating Humidity | 5% to 95% non-condensing |
| Enclosure Type | ABS plastic, 94-V0 fl ammability rating |
| Weight | 340 g (12 ounces) |

Simple Data Analysis with ELOG 2011
The Windows-based ELOG software package is used to program the meter, display metered values, and retrieve and analyze the collected data. ELOG graphically displays recorded data, performs analysis, and facilitates automatic remote data collection.Data is also easily exported to popular spreadsheet and database programs for additional analysis. You are provided with an unlimited site license to the software with purchase.

(Image note: Instantaneous Channel Values: See information about your logger and what your logger is recording in real time)

(Image note: Create many types of graphs within ELOG)
Product brochures
Product manuals
Video
No user reviews available.
Want to Purchase Everything Together? Kits and Bundles below: