Home » Three Phase » ELITEpro portable power datalogger with 3 x 5A CT Bundle
ELITEpro portable power datalogger with 3 x 5A CT Bundle



The Bad:
The Bottom Line:
Full Review
ELITEpro Technical Specifications
3 Voltage Channels.......... 0-600 Volts AC or 0-800
Volts DC, Higher AC voltages can be measured with a Potential
(voltage) Transformer
4 Current Channels.......... 0-333 mV AC or 0-600 mV
DC, Corresponding to 0-6,000+ Amps depending on current transformer
selected
Current Transformers...... Uses voltage output CTs
(0-333mVAC) for maximum safety. Compatible with DENT Instruments DATAproTM and Energy Logger CTs
Measurement
Type...........
True RMS using high-speed digital signal processing (DSP)
Line
Frequency.................
60, 50, or 400 Hz and DC
Harmonic
Sensitivity........
1st through 50th
Waveform
Sampling.........
128 times per cycle
Measurements ................. Volts, Amps, kW,
kVAR, kVA, and Power Factor Maximum, Minimum, Average, (All Parameters) also kWh, kVARh, kVAh, Ah
Harmonics......................... DC and
Fundamental through 50th (odd and even), Total Harmonic Distortion,
Crest Factor, for both Current and Voltage.
Waveform Capture........... Voltage, Current, Power
Accuracy............................ Better
Than 1% (<0.5% typical) for V, A, kW, kVAR, kVA, PF exclusive of sensor error
Resolution......................... 12 bit A/D
plus sign (1 part in 4,096): 0.01 Amp, 0.1 Volt, 1 watt, 1
VAR, 1 VA, 0.01 Power Factor
Memory.............................. 128
kBytes standard (~25,000 readings), or 512 kB (~100,000 readings)
Memory
Types..................
Ring (continuous, write newest over oldest), or Linear (stop when full)
Recording
Intervals..........
3, 15, 30 seconds, 1, 2, 5, 10, 15, 20, 30 minutes and 1, 12, 24 hours
Indicators........................... 2
LEDs: Green to signal when logging, Red to signal low battery
Communication
Direct..............................
RS-232 to PC via 9 pin null modem cable
Communication Rate... 1200, 2400, 4800, 9600, 19200, 28800, 57600 baud
Modem........................... Internal 1200, 2400, 4800, 9600, 14400
baud, auto-answer, auto-dial modes
ELOG Software............. Programs Logger,
Displays Current Metered Values, Retrieves Data
Data
Formats.....................
ASCII and Binary
Power.................................
Internal Lithium Battery; For external power use a Listed (US/Canada) or
Analog
Sampling Rate.....
3 seconds on external DC power, 1 minute when on internal battery
Clock..................................
Mechanical
Operating Temperature. -7 to + 60 oC (20 to 140 oF)
Humidity..........................
5% to 95% non-condensing
Enclosure........................
Indoor: High Impact ABS Plastic, UL 94-V0 flame rating
Outdoor: Weather tight enclosure, Polycarbonate UL 94-V2 flame
rating
Weight..............................
0.4 kg (11 ounces) without modem
Dimensions..................... 8 X 15 X 6 cm (3.2” X 5.9” X 2.4”) Indoor Enclosure