SmartReader Plus 7 Eight Channel Process Signal Data Logger - 10V

Part Number:
ACR SRP-007-0-10V
In Stock?
Stock may be available
please call (877)766-5412 to confirm

Quantity

Price:
$1084.76 USD (change)

 

The ACR SmartReader Plus 7 Eight Channel Process Signal Data Logger is a versatile data logger for easy recording of common process signal variables. With seven input channels, the logger is ideal for monitoring (through commercially available transducers) a wide variety of measurement parameters.
The Good:


The Bad:


The Bottom Line:

Full Review


  • 12 bit resolution
  • 8 channels
  • 10-year battery life
  • Up to 1.5 MB memory
  • User-configurable
  • Accessible remotely by modem
  • Network capable
  • Up to 25 samples per second
Input Ranges - Standard Model 0 to 2.5 volts DC (1 channel)
0 to 5.0 volts DC (2 channels)
0 to 10.0 volts DC (1 channel)
0 to 200 millivolts DC (1 channel)
0 to 25 milliamps DC (2 channels)
Input Ranges - Other Models 0 to 2.5 volts DC (all external channels)
0 to 5 volts DC (all external channels)
0 to 10 volts DC (all external channels)
0 to 25mA DC (all external channels)
Accuracy +/- 0.5% of full scale
Overload Protection Voltage channels: +/- 40 volts (reverse-polarity protected)
Current channels: +/- 70 mA (reverse-polarity protected)
Input Impedance > 1 M ohm (200 mV channels)
> 1 M ohm (0 to 2.5 V channels)
> 1 M ohm (0 to 5.0 V channels)
> 1 M ohm (0 to 10.0 V channels)
20 ohm (0 to 25 mA channels)
Transducer Restrictions It is recommended to use a single power supply or loop isolators to avoid ground loops