Designed by electricians. Engineered by Fluke.
Compact true-rms meter for field service technicians. The Fluke 115 is the solution for a wide variety of electrical and electronic testing applications.
Also check out the
Fluke 114 Electrical Multimeter, the
Fluke 116 HVAC Multimeter with Temperature and Microamps, and the
Fluke 117, the Electrician’s Multimeter with Non-contact voltage.
- AutoVolt: automatic ac/dc voltage selection
- Large white LED backlight to work in poorly lit areas
- Resistance and continuity
- Min/Max/Average to record signal fluctuations
- CAT III 600 V safety rated
Safety conformance
All inputs are protected to CE, IEN61010-1 CAT III 600V. UL, CSA, TÜV listed and VDE.
| Specifications |
| Maximum voltage between any terminal and earth ground | |
| Surge protection |
|
6 kV peak per IEC 61010-1 600 VCAT III, Pollution Degree 2 |
|
| Display |
| Digital: |
6,000 counts, updates 4 per second |
|
| Bar graph |
|
33 segments, updates 32 per second |
|
| Operating Temperature | |
| Storage Temperature | |
| Battery type |
|
9 volt Alkaline, NEDA 1604A/ IEC 6LR61 |
|
| Battery Life |
|
400 hours typical, without backlight |
|
| Accuracy Specifications |
| DC millivolts |
| Range: |
600.0 mV |
| Resolution: |
0.1 mV |
| Accuracy: |
± ([% of reading] + [counts]): 2.0% + 3 |
|
| DC volts |
| Range/Resolution: |
6.000 V / 0.001 V |
| Range/Resolution: |
60.00 V / 0.01 V |
| Range/Resolution: |
600.00 V / 0.1 V |
|
| Auto volts |
| Range: |
600.0 V |
| Resolution: |
0.1 V |
| Accuracy: |
2.0 % + 3 (dc, 45 Hz to 500 Hz)4.0 % + 3 (500 Hz to 1 kHz) |
|
| AC millivolts1 true-rms |
| Range: |
600.0 mV |
| Resolution: |
0.1 mV |
| Accuracy: |
1.0 % + 3 (dc, 45 Hz to 500 Hz)2.0 % + 3 (500 Hz to 1 kHz) |
|
| AC volts1 true-rms |
| Range/Resolution: |
6.000 V / 0.001 V |
| Range/Resolution: |
60.00 V / 0.01 V |
| Range/Resolution: |
600.0 V / 0.1 V |
| Accuracy: |
1.0 % + 3 (dc, 45 Hz to 500 Hz)2.0 % + 3 (500 Hz to 1 kHz) |
|
| Continuity |
| Range: |
600 Ω |
| Resolution: |
1 Ω |
| Accuracy: |
Beeper on < 20 Ω, off > 250 Ω; detectsopens or shorts of 500 μs or longer. |
|
| Ohms |
| Range/Resolution: |
600.0 Ω / 0.1 Ω |
| Range/Resolution: |
6.000 kΩ / 0.001 kΩ |
| Range/Resolution: |
60.00 kΩ / 0.01 kΩ |
| Range/Resolution: |
600.0 kΩ / 0.1 kΩ |
| Range/Resolution: |
6.000 MΩ / 0.001 MΩ |
| Accuracy: |
0.9 % + 1 |
| Range/Resolution: |
40.00 MΩ / 0.01 MΩ |
| Accuracy: |
1.5 % + 2 |
|
Notes:
1) All ac voltage ranges are specified from 1 % to 100% of range. Because inputs below 1 % of range are not specified,
it is normal for this and other true-rms meters to display non-zero readings when the test leads are disconnected
from a circuit or are shorted together. For volts, crest factor of ≤ 3 at 4000 counts, decreasing linearly to 1.5 at full
scale. AC volts is ac-coupled. Auto-V LoZ, and ac mV are dc-coupled.
2) Frequency is ac coupled, 5 Hz to 50 kHz for ac voltage.
| Mechanical & General Specifications |
| Size |
| Height: |
27.62 cm (10.875") |
| Length: |
15.875 cm (6.25") |
| Width: |
5.6 cm (2.203") |
|
| Weight | |
| Warranty | |
No user reviews available.