Amprobe DM-4 Power Quality Recorder

Part Number:
AMP DM-4
In Stock?
Stock may be available
please call (877)766-5412 to confirm

Quantity

Price:
$3495.00 USD (change)

 

The Amprobe DM-4 Power Quality Recorder addresses the needs of the most demanding Power Quality professionals. The device incorporates full set of measuring features crucial for complete Power Quality analysis.  An innovative Remote User Interface (PDA) allows safe, easy and convenient operation of the device remotely.

The Remote User Interface (PDA) is also used for data viewing,analysis and transfer. Independently, the Amprobe DM-4 Power Quality Recorder can be used directly with the PC type of computer.  Since the DM-4does not have any control buttons on its enclosure, it is protected against setup changes by unauthorized persons while the device is recording.

  • True RMS (TRMS)
  • Extremely easy to setup and operate
  • Comes as a complete kit: carrying case, CTs, test leads,PC software & download cable, Remote User Interface PDA) w/ protective hard case and interface cable are included with product
  • Rugged Remote User Interface with memory for easy data downloads in the field and increased safety
  • Works with single (two and three wire) and three phase systems (Y and Delta)
  • Detects and records voltage spikes 100 nS or slower
  • Detects and records voltage Sags and Surges
  • Built in scope displays waveforms
  • Records all parameters (single or three phase) simultaneously
  • Manual and programmable recording start
  • Selectable fundamental frequency of 50 or 60 Hz
  • Special data compression system and user selectable rates allow recording from several hours to several years
  • Download capabilities with PC (Windows compatible software) or PDA (Palm OS)
  • Line or battery powered
  • Safety:  CAT III, 600V
The Good:


The Bad:


The Bottom Line:

Full Review

FEATURES DM-4 ACCURACY
Supplied Current Transducer 1000A Standard CT,
2” internal diameter CT
Input accuracy:
+/-(2% Rdg + 2 LSD)
AC Current Standard CT (DM-CT-HTA): 5 - 1000A
Or optional
Small size CT (DM-CT-100): 1A – 100A
For more CT options visit www.Amprobe.com
AC Voltage including
Sags and Surges
From 20V – to 1000V +/-(3% Rdg + 2 LSD)
Voltage Transients 200-6000Vpp
Duration > 100nS
±10% Rdg
Harmonics (Voltage and Current) THD, DC and individual up to 51th +/-(5% Rdg + 2 LSD) @
DC to 25 harmonics**
Power Working (W), Reactive (VAR) and Apparent (VA) +/-(3.0% Rdg + 2 LSD)
Energy Working (kWh), Reactive (VARh) and Apparent (VAh) +/-(3.0% Rdg + 2 LSD)
Peak Demand KW +/-(3.0% Rdg + 2 LSD)
Power Factor (True and Displacement) 0.00 – 1.00 +/-3%
Phase sequence 1 - 2 - 3  
Selectable Fundamental Frequencies 50/60 Hz  
Available Recording Time Several hours to several years depending on setup  

OPTIONAL ACCESSORIES PART NUMBER
100A Compact Clamp (0.5A to 100A) DM-CT-100
USB-RS-232 Adapter RS-USB

REPLACEMENT PARTS
(supplied with product)
PART NUMBER
1000A Clamp DM-CT-HTA
Remote user interface (PDA) with connection cables Recommended Tungsten E2 Ordered through PALM retailers, visit www.palm.com for details
Remote user interface protective case DM-4CASE
Soft Carrying case HW1254A
External power supply 12VDC DMT-EXTPS
Test leads and alligator clips (set of 4) KITENERGY3
PDA/DM-4 Interface Cable RS-PDA
RS-232 Computer Cable RS-232
PC Windows Software www.amprobe.com
Palm OS Software www.amprobe.com
Instruction Manual www.amprobe.com

Voltage Measurement
Range Accuracy Resolution Input Impedance
20-370V ±(3%+2digit) 0.1V 300k½ (phase-neutral)
310-635V 0.1V 600k½ (phase-phase)

Voltage Anomalies Detection (Manual Selection of Range) Voltage
Range Accuracy Resolution Input Impedance
20-370V ±(3%+2digit) 0.1V 300k½ (phase-neutral)
310-635V 0.1V 600k½ (phase-phase)

Time
Accuracy (ref. to 60Hz) Resolution
±8.33ms (1/2 period of fundamental) 8.33ms (1/2 period of fundamental)

Current Measurement (Using external transducer)
Range Accuracy Resolution Input Impedance Protection against overloads
0.005-0.26V ±(2%+2digit)   100k½ 5V
0.26-1V  
Minimal Current measurable is equal to 0.5% of Clamp Full Scale

Power Measurement (cosQ: 0.5c – 0.5i)
Value Ranges Accuracy
Active Power 0 – 999.9W
1KW – 999.9KW
1MW – 999.9MW
±(3%+2digit)
Reactive Power 0 – 999.9VAR
1KVAR – 999.9KVAR
1MVAR – 999.9MVAR
Apparent Power 0 – 999.9VA
1KVA – 999.9KVA
1MVA – 999.9MVA
Active Energy 0 – 999.9Wh
1KWh – 999.9KWh
1MWh – 999.9MWh
Reactive Energy 0 – 999.9VARh
1KVARh – 999.9KVARh
1MVARh–999.9MVARh

CosQ Measurement
CosQ Resolution Accuracy (expressed in degrees)
0.20 0.01
0.50
0.80

Measurement of Harmonics
Voltage
Range Accuracy Resolution
DC – 25h
26h – 33h
34h – 51h
±(5.0%+2digit)
±(10.0%+2digit)
±(15.0%+2digit)
0.1V
The voltage harmonics will be null under the following threshold:
- DC: if <1V or <2% of 1st harmonic
- 1st harmonic: if <2V
- 2nd - 51st: if <1V or <2% 1st harmonic
Current
DC – 25h
26h – 33h
34h – 51h
±(5.0%+2digit)
±(10.0%+2digit)
±(15.0%+2digit)
0.1A
The voltage harmonics will be null under the following threshold:
- DC: if <2% of 1st harmonic or < 0,2% of clamp full scale
- 1st harmonic: if < 0,2% of clamp full scale
- 2nd - 51st: if<2% 1st harmonic or < 0,2% of clamp full scale

General Characteristics
13.1.7 Temperature Drift
Temperature drift: 0.1 x accuracy/K
13.1.8 Safety
Insulation: Class 2
Pollution: 2
Over-voltage category: CAT III 600V~ (Phase-phase)
CAT II 1000V~ (Phase-Phase)
Mechanical Features
Dimensions: 8.9” (L) x 4.1” (W) x 2.1” (H)
225(L) x 104(W) x 54(H) mm
Weight: 3.3 Lb (1.5kg)
Internal Power Supply: 8 batteries 1.5V series AA
Battery Life: 3-hours
External Power Supply: Use only Amprobe power supply Adapter code DM4EXTPS
Sampling Speed: 83.33 usec at 60Hz
No. of Samples Per Period: 128
Clamp
Opening: 2.15” (53 mm)
Maximum Diameter of The Cable: 2.00” (50 mm)
ENVIRONMENT
Operating conditions
Reference Temperature: 73°F ± 2°F (23°C ± 1°C)
Operating Temperature: 32°F to 122°F (0°C to 50 °C)
Relative Humidity: <70%
Storage Temperature: 14°F to 140°F (-10°C to 60 °C)
Storage Humidity: <80%